10~35kV Overhead Insulated Cable

This product is manufactured according to GB/T14049-2008 "Rated Voltage 10Kv, 35kV Overhead Insulated Cable" and IEC60502 "Rated Voltage 1-30kV Extruded Insulated Power Cable and Accessories" and other standards.
  • Description
  • Product Standards

    This product is manufactured according to GB/T14049-2008 "Rated Voltage 10Kv, 35kV Overhead Insulated Cable" and IEC60502 "Rated Voltage 1-30kV Extruded Insulated Power Cable and Accessories" and other standards.

    Use features

    2.1 Rated voltage

    2.2 The allowable long-term work of the cable conductor does not exceed the temperature:

    HDPE insulated overhead cable: 75℃;

    XLPE insulated overhead cable: 90℃;

    2.3 In case of short circuit (the longest duration does not exceed 5s), the maximum allowable temperature of the cable conductor shall not exceed:

    HDPE insulated overhead cable: 150℃;

    XLPE insulated overhead cable: 250℃;

    2.4 The ambient temperature should not be lower than -20℃ when the cable is laid.

    2.5 Allowable bending radius of cables:

    Single-core cable: should not be greater than 20 times the outer diameter of the cable.

    Multi-core cable: should not be greater than 15 times the outer diameter of the cable.